Pacific DC Intertie

Pacific DC Intertie

The Pacific DC Intertie (also called Path 65) is an electric power transmission line that transmits electricity from the Pacific Northwest to the Los Angeles area using high voltage direct current (HVDC). The line capacity is 3,100 megawatts, which is enough to serve two to three million Los Angeles households and is 48.7% of the Los Angeles Department of Water and Power (LADWP) electrical system's peak capacity. [ cite web
url=http://www.latimes.com/news/local/la-me-power28jul28,0,4534657.story?coll=la-home-headlines
title=Heat Wave Caught DWP Unprepared
publisher = L.A. Times online
date = September 10, 2006
author = Sharon Bernstein and Amanda Covarrubias, Times Staff Writers
accessdate = 2006-09-11
]

The intertie originates near the Columbia River at the Celilo Converter Station on Bonneville Power Administration's (BPA) grid outside The Dalles, Oregon and is connected exclusively to the Sylmar Converter Station north of Los Angeles, which is owned by five utility companies and managed by LADWP. The Intertie is capable of transmitting power in either direction, but power on the Intertie flows mostly from north to south.

The idea of shipping hydroelectric power to Southern California had been proposed as early as the 1930s, but was opposed and scrapped. By 1961, U.S. president John F. Kennedy authorized a large public works project, using new high voltage direct current technology from Sweden. The project was undertaken as a close collaboration between General Electric of the U.S. and ASEA of Sweden. Private California power companies opposed the project but their technical objections were rebutted by Uno Lamm of ASEA at the IEEE meeting in New York in 1963. When completed in 1970 the combined AC and DC transmission system was estimated to save consumers in Los Angeles approximately U.S. $600,000 per day by use of electric power from projects on the Columbia River.

The Pacific Intertie takes advantage of differing power demand patterns between the northwestern and southwestern U.S. During winter, the northern region operates electrical heating devices while the southern portion uses relatively little electricity. In summer, the north uses little electricity while the south reaches peak demand due to air conditioning usage. Any time the Intertie demand lessens, the excess is distributed elsewhere on the western powergrid (states west of the Great Plains, including Colorado and New Mexico). [ cite web
url=http://www.ewh.ieee.org/r7/toronto/events/oct0303/prabha.ppt
format = powerpoint
title = Power System Security in the New Industry Environment: Challenges and Solutions
author = Prabha Kundur, Powertech Labs Inc.
pages = 17
publisher = IEEE
date = October 3, 2003
accessdate = 2006-09-11
]

The Pacific Intertie consists of:
* The Celilo Converter Station which converts three phase 60 Hz AC at 235 to 525 kV to 500 kV DC.
* The grounding system at Celilo consists of 1,067 cast iron anodes buried in a two foot trench of petroleum coke, which behaves as an electrode, arranged in a ring of 3,255 meters (2.02 mi) circumference at Rice Flats (near Rice, Oregon), which is 10.6 km (6.6 mi) SSE of Celilo. It is connected to the converter station by two aerial cables.
* A 1,362 kilometer (846 mile) overhead transmission line consisting of two uninsulated conductors 1,171 mm2 containing a steel wire core for strength.
* The Sylmar Converter Station which converts DC to AC (a process also called inverting) and phase-synchronized with the L.A. power grid.
* The Sylmar grounding system is 24 silicon-iron alloy electrodes submerged in the Pacific Ocean suspended in concrete enclosures about one meter above the ocean floor. The grounding array is 48 km (30 mi) from the converter station.
*The wires have a capacity of 2 gigawatts in bipolar mode and 1.55 gigawatts with earth return. [ cite web
url = http://web.archive.org/web/20050426045806/http://www.transmission.bpa.gov/cigresc14/Compendium/PACIFIC.htm
title = The Pacific Intertie Scheme
publisher = Bonneville Power Administration
date = 2000-11-3
accessdate = 2006-09-10
]

Originally only mercury arc rectifiers were used as static inverter valves. The valves were series connected in three six-pulse valve bridges for each pole. The blocking voltage of the valves was 133 kV with a maximum current of 1,800 amperes, for a transmission rate of 1,440 megawatts with a symmetrical voltage of 400 kV against earth. The line is the DC part of a system of four 500 kV lines that connect the Pacific Northwest with the Southwest; the AC part is Path 15. This is one of two HVDC lines serving Los Angeles, the other is the Intermountain.

*In 1972, after the Sylmar earthquake, the static inverter station in Sylmar had to be reconstructed after damage to the largest part.
*In 1982, the power rating of the mercury arc valve rectifiers was raised by various improvements to 1,600 megawatts.
*In 1984, the transmission voltage was pushed to 500 kV and the transmission power was increased to 2,000 megawatts by adding two six-pulse thyristor valve groups to each pole.
*In 1989, a further increase of the transmission power took place by a parallel switched thyristor static inverter in Celilo and Sylmar.
*In 2004, Sylmar East station was upgraded from 1,100 MW to 3,100 MW (rededicated as the Sylmar Converter Station in 2005). The controls and older converters, including the mercury arc valves, were completely replaced by a single pair of 3,100 MW 12-pulse converters built by ABB. In parallel with this project, the six-pulse mercury arc valves at the Celilo Converter Station were replaced with Siemens light-triggered thyristors (MARP replacement).

ee also

* Uno Lamm
* Intermountain

References

External links

More on the ABB website on Pacific HVDC Intertie:
* [http://www.abb.com/GLOBAL/GAD/GAD02181.NSF/viewUNID/C1256D71001E0037C1256B8000371E41!OpenDocument Abb.com]
* [http://www.abb.com/GLOBAL/GAD/GAD02181.NSF/viewUNID/C1256D71001E0037C1256B81002E886B!OpenDocument Abb.com]
* [http://www02.abb.com/global/gad/gad02007.nsf/Images/36EEF811D43233BBC1256EBD006FB569/$File/L32457_720.jpg?OpenElement aerial photo of Sylmar inverter plant]
* [http://wecc.biz/ Wecc.biz]


Wikimedia Foundation. 2010.

Игры ⚽ Нужна курсовая?

Look at other dictionaries:

  • Pacific DC Intertie — Verlauf der Pacific DC Intertie im Westen der USA Die Pacific DC Intertie, auch als Path 65 bezeichnet, ist eine Hochspannungs Gleichstrom Übertragungsleitung (HGÜ) im Westen der USA welche dazu dient elektrische Energie aus dem Norden der USA in …   Deutsch Wikipedia

  • PDCI —   Pacific DC Intertie …   Energy terms

  • Path 15 — is the name of a major north south power transmission corridor in California. It forms a part of the Pacific AC Intertie and the California Oregon Transmission Project. Path 15, along with the Pacific DC Intertie running far to the east, forms an …   Wikipedia

  • Path 66 — (also called the California Oregon Intertie or abbreviated COI) is the name of several 500 kV power lines that were built by Western Area Power Administration (WAPA), Pacific Gas Electric (PG E), and PacifiCorp in the early 1970s to 1990s and… …   Wikipedia

  • Sylmar, Los Angeles, California — Sylmar is a district in the San Fernando Valley region of the City of Los Angeles, California. It is located east of Interstate 5 and north of the city of San Fernando. Sylmar was once the site of the world’s largest olive groves hence its name,… …   Wikipedia

  • Bonneville Power Administration — The Bonneville Power Administration (BPA) is an American Federal agency based in the Pacific Northwest. BPA was created by an act of Congress in 1937 to market electric power from the Bonneville Dam located on the Columbia River and to construct… …   Wikipedia

  • Intermountain — (also called Path 27) is the designation of a bipolar HVDC transmission line between the Intermountain power plant in Utah and the Adelanto static inverter plant near Adelanto, California. The Intermountain is a bipolar overhead line with a… …   Wikipedia

  • Sylmar Converter Station — is the southern terminal of Pacific DC Intertie at Sylmar, California, USA. It consists of two parts, Sylmar A and Sylmar B. Sylmar A is the older of them. It was built in 1970 and used as valves originally three six pulse groups of mercury arc… …   Wikipedia

  • Celilo Converter Station — The Celilo Converter Station, built in 1970 and owned and operated by the Bonneville Power Administration, is the northern terminus of the Pacific DC Intertie, near The Dalles, Oregon, in the United States.Until September 2001, the Celilo… …   Wikipedia

  • The Dalles, Oregon — The Dalles and the Columbia River as seen from Kelly Viewpoint …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”