Zone valve

Zone valve

A zone valve is a specific type of valve used to control the flow of water or steam in a hydronic heating or cooling system.

In the interest of improving efficiency and occupant comfort, such systems are commonly divided up into multiple zones. For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.

This zoning can be accomplished in one of two ways:
* Multiple circulator pumps, or
* A single circulator pump and zone valves.

Zone valve construction and operation

Zone valves as used in home hydronic systems are usually electrically powered. In large commercial installations, vacuum or compressed air may be used instead. In either case, the motor is usually connected to the water valve via a mechanical coupling.

For electrical zone valves, the motor is often a small shaded-pole synchronous motor combined with a rotary switch that can disconnect the motor at either of the two stopping points ("valve open" or "valve closed"). In this way, applying power to the "open valve" terminal causes the motor to run until the valve is open while applying power at the "close valve" terminal causes the motor to run until the valve is closed. The motor is commonly powered from the same 24 volt ac power source that is used for the rest of the control system. This allows the zone valves to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. This style of valves requires the use of an SPDT thermostat or relay.

Zone valves can also be constructed using wax motors and a spring-return mechanism. In this case, the valve is normally closed by the force of the spring but can be opened by the force of the wax motor. Removal of electrical power re-closes the valve. This style of zone valve operates with a perfectly ordinary SPST thermostat.

For vacuum- or pneumatically-operated zone valves, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm to move and actuate the valve. Unlike the electrical zone valves, these valves automatically return to the default position without the application of any power, and the default position is usually "open", allowing heat to flow.

Highly sophisticated systems may use some form of building automation such as BACnet or LonWorks to control the zone valves.

Comparison with multiple circulator pumps

Multiple zones can be implemented using either multiple, individually-controlled circulator pumps or a single pump and multiple zone valves. Each approach has advantages and disadvantages.

Multiple Pump System

Advantages:
* Simple mechanical and control design ("SPST thermostats")
* Redundancy: If one zone pump fails, the others can remain working

Disadvantages:
* Higher initial installation cost. Circulator pumps cost more than zone valves
* Higher power consumption. Operating circulators draw substantial power any time the zone is actively heating. Zone valves, by comparison, draw little power at any time and many designs only draw power while in transition from open to close or vice-versa.

Zone Valve System

Advantages:
* Lower initial installation cost.
* Lower power consumption.

Disadvantages:
* Zone valves can be unreliable. Zone valves operated by electric timing motors aren't "fail safe" (failing to the "open" condition).
* No inherent redundancy for the pump. A zone-valved system is dependent upon a single circulator pump. If it fails, the system becomes completely inoperable.
* The system can be harder to design, requiring both "SPDT" thermostats or relays and the ability of the system to withstand the fault condition whereby all zone valves are closed simultaneously.

Typical manufacturers of zone valves:

* Mut Meccanica
* Taco
* Honeywell
* Boss

See also

* Zone damper


Wikimedia Foundation. 2010.

Игры ⚽ Нужно решить контрольную?

Look at other dictionaries:

  • Valve — This article is about the flow control device. For the game developer, see Valve Corporation. For the electronic component, see Vacuum tube. For other uses, see Valve (disambiguation). These water valves are operated by handles. A valve is a… …   Wikipedia

  • Double check valve — A double check valve or double check assembly (DCA) is a backflow prevention device designed to protect water supplies from contamination. It is also a valve used in air brake systems on heavy trucks. Usage in Water Supply: In the case of usage… …   Wikipedia

  • Reduced pressure zone device — A Reduced Pressure Zone Device (RPZD, RPZ or RPZ valve) is a type of backflow prevention device used to protect water supplies from contamination. An RPZD is considered suitable for high hazard applications, that is, where the consequence of… …   Wikipedia

  • Ball valve — Ball Ball (b[add]l), n. [OE. bal, balle; akin to OHG. balla, palla, G. ball, Icel. b[ o]llr, ball; cf. F. balle. Cf. 1st {Bale}, n., {Pallmall}.] 1. Any round or roundish body or mass; a sphere or globe; as, a ball of twine; a ball of snow. [1913 …   The Collaborative International Dictionary of English

  • Hydronics — is the name for the use of water as the heat transfer medium in heating and cooling systems. Some of the oldest and most common examples are steam and hot water radiators. In large scale commercial buildings such as high rise and campus… …   Wikipedia

  • Damper (flow) — This article is about the architectural element. For other uers, see Damper (disambiguation). Opposed blade dampers in a mixing duct. A damper is a valve or plate that stops or regulates the flow of air inside a duct, chimney, VAV box, air… …   Wikipedia

  • Damper (architecture) — A damper is a valve or plate that stops or regulates the flow of air inside a duct, chimney, VAV box, air handler, or other air handling equipment. A damper may be used to cut off central air conditioning (heating or cooling) to an unused room,… …   Wikipedia

  • Circulator pump — A circulator pump is a specific type of pump used to circulate gases, liquids, or slurries in a closed circuit. They are commonly found circulating water in a hydronic heating or cooling system. Because they only circulate liquid within a closed… …   Wikipedia

  • отключающий кран — Кран, управляемый вручную или автоматически, который в закрытом состоянии предотвращает движение газа в обоих направлениях. [ГОСТ Р 52423 2005] Тематики ингаляц. анестезия, искусств. вентиляц. легких EN isolating valveshut off valvezone valve DE… …   Справочник технического переводчика

  • WMZV-4 — * Weil McLain Zone Valve 4 Zone (Business » Firms) …   Abbreviations dictionary

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”