Seasonal energy efficiency ratio

Seasonal energy efficiency ratio

The efficiency of air conditioners is often rated by the Seasonal Energy Efficiency Ratio (SEER) which is defined by the [Air Conditioning, Heating, and Refrigeration Institute] in its standard ARI 210=240, Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment. [http://ari.org/Content/FindaStandard_218.aspx?Listing_PK=160] The higher the SEER rating of a unit, the more energy efficient it is. The SEER rating is the Btu of cooling output during a typical cooling-season divided by the total electric energy input in watt-hours during the same period.

For example, a 5000 Btu/h air-conditioning unit, with a SEER of 10, operating for a total of 1000 hours during an annual cooling season (e.g., 8 hours per day for 125 days) would provide an annual total cooling output of:

:5000 BTU/h × 1000 h = 5,000,000 Btu

With a SEER of 10, the annual electrical energy usage would be about:

:5,000,000 BTU / 10 BTU/W·h = 500,000 W·h

The average power usage may also be calculated more simply by:

:Average power = (Btu/h) / (SEER, Btu/W·h) = 5000 ÷ 10 = 500 W"'

If your electricity cost is 20¢/kWh, then your operating cost is:

:0.5 kW × 20¢/kWh = 10¢/h

Relationship of SEER to EER and COP

SEER is related to the Energy Efficiency Ratio (EER), which is the ratio of "output" cooling in Btu/Hr and the "input" power in watts W at a given operating point and also to the COP commonly used in thermodynamics. Performance ratios can be a unitless output over input ratio, never to exceed one, and it is also proper to state what kind of energy is in the numerator and denominator. The COP of a heat pump is determined by dividing the power output of the heat pump by the electrical power needed to run the heat pump, with both powers measured using the same units, e.g. watts. The higher the COP, the more efficient the heat pump. For example resistive heat has a COP = 1. The EER is the efficiency rating for the equipment at a particular pair of external and internal temperatures. EER ((Btu/(W*hr)) is converted to COP (Btu/Btu) by dividing by 3.413 Btu/(Hr*W).

The SEER is calculated over a range of expected external temperatures (i.e., the temperature distribution for the geographical location of the SEER test).

From equation (2) above, a SEER of 13 is approximately equivalent to a COP of 3.43, which means that 3.43 units of heat energy are removed from indoors per unit of work energy used to run the heat pump.

Theoretical maximum

The SEER and EER of an air conditioner are limited by the laws of thermodynamics. The refrigeration process with the maximum possible efficiency is the Carnot cycle. The COP of an air conditioner using the Carnot cycle is:

:COP_{Carnot}=frac{T_{C{T_{H}-T_{C

where T_C is the indoor temperature and T_H is the outdoor temperature. Both temperatures must be measured using a thermodynamic temperature scale such as Kelvin or Rankine. The EER is calculated by multiplying the COP by 3.413:

:EER_{Carnot}=3.413 frac{T_{C{T_{H}-T_{C

For an indoor temperature of 80F (299.81 K) and an outdoor temperature of 95F (308.15 K), the above equation gives an COP of 36.0. This is about 3 times more efficient than a typical home air conditioner available today.

The maximum COP decreases as the difference between the inside and outside air temperature increases, and vice versa. In desert climates, where the temperature may be as high as 120F, the maximum COP drops to 13.5 (assuming an outdoor temperature of 120F and an indoor temperature of 80F).

The maximum SEER can be calculated by averaging the maximum EER over the range of expected temperatures for the season.

US government SEER standards

SEER rating more accurately reflects overall system efficiency on a seasonal basis and EER reflects the system’s energy efficiency at peak day operations. Both ratings are important when choosing products. As of January 2006, all residential air conditioners sold in the United States must have a SEER of at least 13. ENERGY STAR qualified Central Air Conditioners must have a SEER of at least 14.

Today, it is rare to see systems rated below SEER 9 in the United States because aging, existing units are being replaced with new, higher efficiency units. The United States now requires that residential systems manufactured after 2005 have a minimum SEER rating of 13, although window units are exempt from this law so their SEERs are still around 10.

Substantial energy savings can be obtained from more efficient systems. For example by upgrading from SEER 9 to SEER 13, the power consumption is reduced by 30% (equal to 1 - 9/13). It is claimed that this can result in an energy savings valued at up to US$300 per year depending on the usage rate and the cost of electricity.

With existing units that are still functional and when the time value of money is considered, most often retaining existing units rather than proactively replacing them is the most cost effective. Maintenance should be performed regularly to keep their efficiencies as high as possible.

But when either replacing equipment, or specifying new installations, a variety of SEERs are available. For most applications, the minimum or near-minimum SEER units are most cost effective, but the longer the cooling seasons, the higher the electricity costs, and the longer the purchasers will own the systems, incrementally higher SEER units are justified. Residential split-system ACs of SEER 20 or more are now available, but at substantial cost premiums over the standard SEER 13 units.

Calculating the annual cost of power for an air conditioner

Air conditioner sizes are often given as "tons" of cooling where 1 ton of cooling is defined as being equivalent to 12,000 BTU/h. The annual cost of electric power consumed by a 72,000 BTU/h (6 ton) air conditioning unit operating for 1000 hours per year with a SEER rating of 10 and a power cost of 12¢ per kilowatt-hour (kW·h) may be calculated as follows:

:unit size, BTU/h × hours per year, h × power cost, $/kW·h ÷ SEER, BTU/W·h ÷ 1000 W/kWExample::(72,000 BTU/h) × (1000 h) × (12¢/kW·h) ÷ (10 BTU/W·h) ÷ (1000 W/kW) = $864 annual cost

As another example, a 2000 ft2 residential unit near Chicago would require a 4 ton air conditioner based on a location-specific rule-of-thumb that 1 ton is required for each 500 ft2 for a typical older house:

:(2000 ft2) ÷ (500 ft2/ton) = 4 tons.

:(4 tons) × (12,000 BTU/h/ton) = 48,000 BTU/h.

The estimated cost of electrical power for the 4 ton unit with a SEER rating of 10 and a power cost of 10¢ per kilowatt-hour, using 120 days of 8 hours/day operation, would be:

: (48,000 Btu/h) × (960 h/year) × (10¢/kW·h) ÷ (10 BTU/W·h) ÷ (1000 W/kW) = $461 annual cost


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать курсовую

Look at other dictionaries:

  • Seasonal Energy Efficiency Ratio — (SEER)   A measure of seasonal or annual efficiency of a central air conditioner or air conditioning heat pump. It takes into account the variations in temperature that can occur within a season and is the average number of Btu of cooling… …   Energy terms

  • Seasonal energy efficiency ratio — (SEER)   Ratio of the cooling output divided by the power consumption. It is the Btu of cooling output during its normal annual usage divided by the total electric energy input in watt hours during the same period. This is a measure of the… …   Energy terms

  • seasonal energy efficiency ratio — (SEER) A measure of cooling capacity …   Dictionary of automotive terms

  • List of energy abbreviations — This is a list of abbreviations found in the context of energy issues. Contents: 0–9 A B C D E F G H I J K L M N O P Q R S T U V W X Y …   Wikipedia

  • Zero-energy building — BedZED zero energy housing in the UK A zero energy building, also known as a zero net energy (ZNE) building, Net Zero Energy Building (NZEB), or Net Zero Building, is a popular term to describe a building with zero net energy consumption and zero …   Wikipedia

  • Annual fuel utilization efficiency — The annual fuel utilization efficiency (AFUE; pronounced A Few ) is a thermal efficiency measure of combustion equipment like furnaces, boilers, and water heaters. The AFUE differs from the true thermal efficiency in that it is not a steady state …   Wikipedia

  • EER, SEER —   Energy Efficiency Ratio, Seasonal Energy Efficiency Ratio …   Energy terms

  • SEER —   See Seasonal Energy Efficiency Ratio (Seasonal Energy Efficiency Ratio)   The total cooling output of a central air conditioning unit in Btus during its normal usage period for cooling divided by the total electrical energy input in watt hours… …   Energy terms

  • Annual Fuel Utilization Efficiency — (AFUE)   The measure of seasonal or annual efficiency of a residential heating furnace or boiler. It takes into account the cyclic on/off operation and associated energy losses of the heating unit as it responds to changes in the load, which in… …   Energy terms

  • Solar thermal energy — Solar thermal system for water heating in Santorini, Greece …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”